Adopt electrical copper conductor, 90℃ XLPE insulation, steel tape armor, PVC outer sheath.
Use characteristics:
1. The maximum rated temperature of the cable conductor is 90℃
2. During short circuit (the longest duration does not exceed 5s), the maximum temperature of the cable conductor does not exceed 250°C.
3. The ambient temperature when laying the cable should not be lower than 0°C
4. The minimum bending radius during installation: a single-core cable is not less than 15 times the outer diameter of the cable, and a three-core cable is not less than 12 times the outer diameter of the cable. The minimum bending radius of the cable near the connection box and the terminal (bending should be carefully controlled, such as using a forming guide plate) single-core cable is not less than 12 times the outer diameter of the cable, and three-core cable is not less than 10 times the outer diameter of the cable.